EOT40/400/5/5/1

General Data

Type EOT40/400/5/5/1
Wire termination Technology Free leads with 2.5 mm² Ring Lug
GTIN / Harmonize Custom Code 85389000
Country of Origin India

Depth (mm) 25
Inner Diameter (inches) 40
Outer Diameter (inches) 75

Ratio 400/5
Rated Burden (VA) 5
Class of Accuracy 1
Rated Frequency (Hz) 50/60
Maximum Operating Voltage (V) 720
Insulating Class E
Rated Insulation Test Voltage 3/4 kV AC for 1 Minute
Instrument Security Factor FS FS 5 or 10
Rated Thermal Short Time Current For BPL (mm²) Ith = 60*Ipr
Rated Thermal Continuous Current Icth = 1.2*Ipr
Rated Thermal Surge Current Idyn = 2.5*Ith
Permissible Humidity Operation <95% RH
Ambient Temperature Operation -20°C ... +50°C
Ambient Temperature Storage -40°C ... +70°C
Max Altitude =1000 m
ROHS NO
Din Rail Mounting Option -
CE Yes
Mounting Plate Available on request
Terminal Cover Without Sealing